Call Toll Free: 800-457-4950
Home » Our Products » Timer » Interval

Switch Adjustable Interval Timing Module

Model No. 4300SA Description:
The model 4300SA series provides a load circuit with operating voltage for a predetermined amount of time each time the operating voltage is applied. The operating voltage must be present for the duration that exceeds the preset timing period. The 4300SA series is available in both AC and DC models and controls output load circuits to 1 ampere. The DIP switch is used to set the desired delay, 3 ranges cover 0.1-102.4 seconds, 1-1024 seconds (std), and 2-2048 seconds.
Type Function Industries
Timer Interval

Operating Voltage 5, 12, 24, 48V DC or 12, 24, 48, 115, 230V AC, 50/60Hz.
Output 10 milliamperes to 1 Amperes inductive with Inrush current to 25 amperes for 8 milliseconds.
Timing Mode Interval
Timing Range 1-1024 seconds, 0.1-102.4 seconds (-1), 2-2048 seconds (-2)
Repeatability Of Timing Periods +/- 1% nominal.
Recycle Time 200 milliseconds minimum